High-Voltage Current-limiting Fuse For Protection Of Transformer

High-Voltage Current-limiting Fuse For Protection Of Transformer

It can be used in indoor system of 50Hz and rated voltage of 3.6KV, 7.2KV, 12KV, 24KV and 40.5KV. Used together with other switch facilities such as loading switches, vacuum contactors, it can protect electric transformers and other electric facilities against overloading or circuit break. It is also a necessary accessory for high-voltage switch. 
high voltage current limiting fuse for protection of transformer 1

Type

Counterpart

Rated voltage (KV)

Rated current of the fuse (A)

Rated current of the fuse link (A)

XRNT-12

SDLAJ

12

40

3.15、6.3、10、16.20、25、31.5、40

XRNT-12

SFLAJ

12

100

50、63、71、80、100、(125)

XRNT-12

SKLAJ

12

125

125.160、200、250

XRNT-24

 

24

200

3.15、6.3、10、16、20、25、31.5、40、50、63、8o、100、125、160、200

XRNT-40.5

 

40.5

125

3.15、6.3、10、16、20、25、31.5、40、50、63、80、100、125

high voltage current limiting fuse for protection of transformer 2 high voltage current limiting fuse for protection of transformer 3 high voltage current limiting fuse for protection of transformer 4

Basic parameters

The basic parameters of the fuser are shown in Table 1 and Table 2


Main technical data

(1) The fuse should be able to break any fault current between the minimum breaking current l3 and the maximum breaking current h. ls current is about 4 times the rated current
(2) The time-current characteristics are shown in Figure 1, and the part above the minimum breaking current l3 is the dotted line


Shape and installation dimensions

The appearance and installation dimensions of the fuse are shown in chat2, chat3, chat4
 

Table1

Type

Rated voltage (A)

Fuse rated current (A)

Main parameters (mm)

Rated maximum breaking current (kA)

Dimensions

length

diameter

BFY□-40.5KV/□A

40.5

3.15、6.3、10、16、20、25、31.5、40、50

3.15、6.3、10、16、20、25、31.5、40、50

650

Φ76

31.5

Plug-in type see Figure 2

Bus type see Figure 3

XRNT□-40.5 KV/□A-31.5-1

3.15、6.3、10、16、20、25、31.5、40、50

See picture 4

high voltage current limiting fuse for protection of transformer 5

◆Technique data

Type

Rated voltage UN (KV)

Rated current  IN(A)

Diameter×Length (mm)

Rated breaking current [KA)

XRNT1

3.6/7.2

6.3

Φ50X192

Standard size

63

10

16

20

25

31.5

40

50

63

Φ76X192

Standard size

80

100

125

160

Φ88X192

Standard size

*200

50

*250

6.3

Φ51X292

Standard size

63

10

16

20

25

31.5

40

50

63

Φ76X292

Standard size

80

100

125

160

Φ88X292

Standard size

50

*200

*250

*315

*355

100

Φ76X442

63

125

160

Φ88X442

*200

50

*250

*315

*355

*400

*500

 

Type

Rated voltage UN (KV)

Rated current  IN(A)

Diameter×Length (mm)

Rated breaking current [KA)

Foreign reference model

XRNT1

6/12

6.3

Φ51X192

63

SDLAJ

10

16

20

Φ76X192

25

31.5

40

2

Φ51X292

Standard size

3.15

6.3

10

20

31.5

40

50

Φ63X292

Φ76X292

Standard size

SFLAJ

63

80

100

125

SKLAJ

*160

Φ88X292

Standard size

50

 

*200

6.3

Φ51X442

63

High-voltage current-limiting fuse for high-voltage center cabinet

10

16

20

25

31.5

40

50

Φ76X442

Standard size

63

80

100

125

160

Φ88X442

Standard size

*200

50

*250

(*) Please pay attention to the use of derating, please refer to the reasonable selection of fuse.

 

Type

Rated voltage UN( KV)

Rated current IN(A)

Diameter×length (mm)

Rated breaking current (KA)

XRNT1

20/24

6.3

Φ53X442 Standard size

 

10

16

63

20

25

31.5

40

50

Φ63X442 Standard size

63

80

100

125

Φ88X442 Standard size

40

160

200

36/40.5

6.3

Φ51X442

31.5

10

16

6.3

Φ51X537 Standard size

40

10

16

20

25

Φ76X537 Standard size

31.5

40

50

Φ88X537 Standard size

63

80

160

(*) Please pay attention to the use of derating, please refer to the reasonable selection of fuse.

 

Transformer capacity KVA

Transformer primary voltage 7.2kV

Fuse rated voltage KV

Fuse rated current A

100

7.2

20

125

20

160

25

200

31.5

250

40

300/315

50

400

71

500

80

630

100

750/800

140

1000

160

1250

200

 

Transformer capacity KVA

Transformer primary voltage 12kV

Fuse rated voltage KV

Fuse rated current A

100

12

16

125

16

160

16

200

20

250

25

300/315

31.5

400

40

500

50

630

63

750/800

80

1000

100

1250

125

1500/1600

160

2000

200

 

Transformer capacity KVA

Transformer primary voltage 24kV

Fuse rated voltage KV

Fuse rated current A

100

24

6.3

125

6.3

160

10

200

10

250

16

300/315

16

400

20

500

25

630

31.5

750/800

40

1000

50

1250

63

15000/1600

80

2000

100

2500

125

3150

160

4000

200

 

Transformer capacity KVA

Transformer primary voltage 12kV

Fuse rated voltage KV

Fuse rated current A

50

35

2

100

3.15

125

5

160

5-6.3

200

6.3

250

8-10

315

10-12

400

12-16

500

16

630

20-25

800

25-31.5

1000

31.5-40

1250

40-50

1600

50

2000

63

 

high voltage current limiting fuse for protection of transformer 6 high voltage current limiting fuse for protection of transformer 7 high voltage current limiting fuse for protection of transformer 8 high voltage current limiting fuse for protection of transformer 9 high voltage current limiting fuse for protection of transformer 10

Type

Equivalent model

Rated voltage (kV)

Fuse rated current (A)

Main parameters (mm)

Rated maximum breaking current (kA)

C

ΦD

XRNT□-3.6

ADF*□

3.6

6.3、10、16、20、25、31.5、40

254

Φ51

50

ADG*□

6.3、10、16、20、25、31.5、40、50、63、80、100

359

XRNT□-7.2

ADF*□

7.2

6.3、10、16、20、25、31.5、40、50、63

254

BDG*□

6.3、10、16、20、25、31.5、40、50、63、80

359

AFF*□

80、100

254

Φ76

BFG*□

100

359

BKG*□

125、140、160

XRNT□-12

BDG*□

12

6.3、10、16、20、22.4、25、31.5 、35.5、40、45、50

359

Φ51

XRNT□-12

BFG*□

12

56、63、71、80、90、100

359

Φ76

AKG*□

112、125

AKG*□

160、200

Φ88

Note: 1. The above are the rated parameters of a single tube. A fixed structure can be used to connect the fuse in parallel according to user needs to obtain a high rated current value;
          2. "Represents different types of impactors.

Main technical data

(3) The fuse should be able to break any fault current between the minimum breaking current l3 and the rated maximum breaking current.
●The fuse below the rated current 125A does not include 125A l3 current is about 4 times the rated current.
●Rated current above 125A includes 125A l3 current is about 7 times the rated current.
(4) The time-current characteristic is shown in Figure 1, and the part above the minimum breaking current is the dotted line.


Shape and installation dimensions

The appearance and installation dimensions of the fuse are shown in Figure 2 to Figure 8.


Selection of fuse

The general selection of fuses for the primary side of the transformer is shown in Table 2

Table2

Transformer capacity KVA

Transformer primary voltage 3.6KV

Fuse rated voltage KV

Fuse rated current A

100

3.6

31.5

125

40

1160

50

200

63

250

80

300/315

90

 

Transformer capacity KVA

Transformer primary voltage 3.6KV

Fuse rated voltage KV

Fuse rated current A

100

7.2

20

125

20

160

25

200

31.5

250

40

300/315

50

400

71

500

80

630

100

750/800

140

1000

160

 

Transformer capacity KVA

Transformer primary voltage 3.6KV

Fuse rated voltage KV

Fuse rated current A

100

12

16

125

16

160

16

200

20

250

25

300/315

31.5

400

40

500

50

630

63

750/800

71

1000

90

1250

112

1500/1600

125

Contact the manufacturer for the selection of transformers in special cases and the selection of other power equipment.

high voltage current limiting fuse for protection of transformer 11 high voltage current limiting fuse for protection of transformer 12 high voltage current limiting fuse for protection of transformer 13 high voltage current limiting fuse for protection of transformer 14 high voltage current limiting fuse for protection of transformer 15

> Hot Products

News Center

> What are the two functions of fuse cutout

The two functions of a fuse are overcurrent protection and isolation. The function of a fuse cu...

> What material are high voltage fuse links made of

High voltage fuse links is composed of conductor material, insulating material and circuit brea...

> Describe the structure, working principle and types of high-voltage fuses

The structural components of high-voltage fuses mainly include melt, fuse tube, contact conduct...

> How to choose a fuse link

As we all know, fuses are the most commonly used protection devices in power systems. So how to...

> How does a low-voltage fuse work? Decipher the working principle and function of the fuse!

How does a low-voltage fuse work? Decipher the working principle and function of the fuse!A fus...

> How many kv are high voltage fuses widely used in?What does N stand for in the high voltage fuse model?

How many kv are high voltage fuses widely used in?High-voltage fuses are widely used in 3-35kV ...

> Factors affecting the price of the fuse, how to judge whether the fuse is blown

Shanghai Zhiguang Fuse Co., Ltd provides related answers to questions such as what are the fact...

> Low-voltage fuse manufacturer knowledge answer: how to measure fuse blowing?

Welcome to Shanghai Zhiguang Fuse Co., Ltd. We are a low-voltage fuse manufacturer in China. Ma...